device.bacnet
BACnet device
type |
object |
||||
properties |
|||||
|
A BACnet Device Identifier is a unique value assigned to each device on a BACnet network. This parameter defines the identifier of the remote BACnet device with which communication is established. When multiple osp-bacnet modules are instantiated, each module must be configured with a unique Device Identifier. Example: 20001. |
||||
type |
integer |
||||
|
Default value is [true] |
||||
type |
boolean |
||||
default |
True |
||||
|
When a device is connected, the first step is to retrieve the list of supported protocols, then to fetch the objectList from the device. This feature is mandatory for using propertiesAcquisionRules and notificationRules. By default, the recommend setting is to keep this option enabled and disabling it only if communication errors occur with the device. Default value is [true] |
||||
type |
boolean |
||||
default |
True |
||||
|
When a device is connected, the first step is to retrieve the list of supported protocols. This retrieval allows the use of more advanced requests based on the device capabilities. Some devices do not support this request (fetch protocolServicesSupported property) or implement it incorrectly. For this reason, it is possible to disable the supported-protocols retrieval. By default, the recommend setting is to keep this option enabled and disabling it only if communication errors occur with the device, as enabling this feature reduces network traffic. Default value is [true] |
||||
type |
boolean |
||||
default |
True |
||||
|
When a COV (Change of Value) subscription request is performed, some properties can be subscribed using a single request. This feature is enabled when protocolServicesSupported reports the SubscribeCovPropertyMultiple capability, allowing multiple properties to be subscribed at the same time. Some devices report this capability but do not implement it correctly, or report support without actually supporting the feature. In such cases, it is possible to force the use of single-property requests by setting this parameter to false. Indicates whether the aggregator should use the multiples COV in a single request. This features is by used if the device report usage supported, but as some device return true, but doesn’t support this features, it’s possible to change the behavior statically by setting to false This option has no effect when the device reports its capabilities via protocolServicesSupported. Default value is [true] |
||||
type |
boolean |
||||
default |
True |
||||
|
When a ReadProperty request is performed, some properties can be retrieved using a single request. This feature is enabled when protocolServicesSupported reports the ReadPropertyMultiple capability, allowing multiple properties to be fetched at the same time. Some devices report this capability but do not implement it correctly, or report support without actually supporting the feature. In such cases, it is possible to force the use of single-property requests by setting this parameter to false. By default, the recommend setting is to keep this option enabled and disabling it only if communication errors occur with the device. This option has no effect when the device reports its capabilities via protocolServicesSupported. Default value is [true] |
||||
type |
boolean |
||||
default |
True |
||||
|
Name of the playbook that generated this file. If present, the file is managed by the Composer and may be overwritten on regeneration. Used for selective clean. Do not edit or set manually. |
||||
type |
string |
||||
|
By default, multiple requests (COV and pollingMultiStrategy) are executed using the limits defined by the target device’s protocolServicesSupported configuration. When this information is not available or not supported by the device, this option allows you to define a custom limit, specifying how many properties or subscriptions are included in a single request. This option has no effect when the device reports its capabilities via protocolServicesSupported. Default value is [10] |
||||
type |
integer |
||||
default |
10 |
||||
|
The BACnet module module.bacnet ↗️ that will be used to communicate. For example modules.bacnet.bacnet-1 is the default OnSphere path of the BACnet module. |
||||
type |
string |
||||
|
Configuration for BACnet notifications class either from rules (dynamic) and for notification.bacnet files. For more information about notification subscription rules ↗️. Default value is [{“autoAcknowledgeAlarms”:false,”autoAcknowledgeEvents”:true,”defaultSubscriptionParameter”:{“bacnetTransitions”:[“TO_OFF_NORMAL”,”TO_FAULT”,”TO_NORMAL”],”confirmedDelivery”:true,”days”:[“MONDAY”,”TUESDAY”,”WEDNESDAY”,”THURSDAY”,”FRIDAY”,”SATURDAY”,”SUNDAY”],”fromTime”:{“hour”:0,”hundredth”:0,”minute”:0,”second”:0},”toTime”:{“hour”:23,”hundredth”:99,”minute”:59,”second”:59}},”subscriptionMethod”:”RECIPIENT_LIST_REGISTER”,”subscriptionRefreshFrequency”:{“unit”:”SECONDS”,”value”:300}}] |
||||
default |
autoAcknowledgeAlarms |
False |
|||
autoAcknowledgeEvents |
True |
||||
defaultSubscriptionParameter |
bacnetTransitions |
TO_OFF_NORMAL |
|||
TO_FAULT |
|||||
TO_NORMAL |
|||||
confirmedDelivery |
True |
||||
days |
MONDAY |
||||
TUESDAY |
|||||
WEDNESDAY |
|||||
THURSDAY |
|||||
FRIDAY |
|||||
SATURDAY |
|||||
SUNDAY |
|||||
fromTime |
hour |
0 |
|||
hundredth |
0 |
||||
minute |
0 |
||||
second |
0 |
||||
toTime |
hour |
23 |
|||
hundredth |
99 |
||||
minute |
59 |
||||
second |
59 |
||||
subscriptionMethod |
RECIPIENT_LIST_REGISTER |
||||
subscriptionRefreshFrequency |
unit |
SECONDS |
|||
value |
300 |
||||
|
Rules define how properties are fetched based on the device’s configuration and values. For example, if a device reports 10 objects and a rule specifies subscribing to all presentValue properties, this results in 10 subscriptions, one per object. If the device later changes to 8 objects, the system will automatically adjust, resulting in 8 subscriptions after detecting the configuration change. |
||||
|
Configuration for the device health monitoring (supervision). It defines the method and frequency used to detect if the device is still reachable on the network. For more information about supervision ↗️. Default value is [{“delayBetweenRetriesMs”:{“unit”:”MILLISECONDS”,”value”:500},”maxRetriesBeforeError”:3,”method”:”OBJECT_NAME”,”monitoringFrequency”:{“unit”:”SECONDS”,”value”:30},”sleepBeforeFirstConnection”:{“unit”:”SECONDS”,”value”:0}}] |
||||
default |
delayBetweenRetriesMs |
unit |
MILLISECONDS |
||
value |
500 |
||||
maxRetriesBeforeError |
3 |
||||
method |
OBJECT_NAME |
||||
monitoringFrequency |
unit |
SECONDS |
|||
value |
30 |
||||
sleepBeforeFirstConnection |
unit |
SECONDS |
|||
value |
0 |
||||
|
The id of the template to use for this file |
||||
type |
string |
||||
|
The variables and their values to be replaced from the template |
||||
type |
object |
||||
additionalProperties |
|||||
|
The variables files to use to replace the variables. The first file of the list will take precedence over the following one. Template variables take precedence over the contents of the files. |
||||
type |
array |
||||
items |
type |
string |
|||
additionalProperties |
False |
||||
NotificationsConfiguration
type |
object |
|||
properties |
||||
|
In BACnet systems, events are generally acknowledged automatically by machines or supervisory logic, while alarms are intended to be acknowledged by a human operator. Notification Classes may require acknowledgement. When this is the case, two different behaviors are supported:
The autoAcknowledgeAlarms parameter allows this behavior to be adjusted. When enabled, alarms are acknowledged automatically, making them behave like events; when disabled, acknowledgement is required even for alarms Default value is [false] |
|||
type |
boolean |
|||
default |
False |
|||
|
In BACnet systems, events are generally acknowledged automatically by machines or supervisory logic, while alarms are intended to be acknowledged by a human operator. Notification Classes may require acknowledgement. When this is the case, two different behaviors are supported:
The autoAcknowledgeEvents parameter allows this behavior to be adjusted. When enabled, events are acknowledged automatically; when disabled, acknowledgement is required even for events, making them behave like alarms. Default value is [true] |
|||
type |
boolean |
|||
default |
True |
|||
|
When a notification is triggered, a linked action will be executed. The data provided when a notification triggered gonna be in the linked action including the properties to fetch. If a specific action is defined in the subscription rules, this default action will be overridden. For more information about notification subscription rules ↗️. |
|||
|
Define which properties should be fetched from the object that triggered the notification. It’s useful to fetch additional context information about the event that triggered the notification. If a specific set of properties is defined in the subscription rules, this default set will be overridden. |
|||
|
The parameter of the subscription defining when the notification should be triggered. If the notification is triggered but the current time is outside of the defined parameter, no action will be executed. If a specific action is defined in the subscription rules, this default action will be overridden. Default value is [{“bacnetTransitions”:[“TO_OFF_NORMAL”,”TO_FAULT”,”TO_NORMAL”],”confirmedDelivery”:true,”days”:[“MONDAY”,”TUESDAY”,”WEDNESDAY”,”THURSDAY”,”FRIDAY”,”SATURDAY”,”SUNDAY”],”fromTime”:{“hour”:0,”hundredth”:0,”minute”:0,”second”:0},”toTime”:{“hour”:23,”hundredth”:99,”minute”:59,”second”:59}}] |
|||
default |
bacnetTransitions |
TO_OFF_NORMAL |
||
TO_FAULT |
||||
TO_NORMAL |
||||
confirmedDelivery |
True |
|||
days |
MONDAY |
|||
TUESDAY |
||||
WEDNESDAY |
||||
THURSDAY |
||||
FRIDAY |
||||
SATURDAY |
||||
SUNDAY |
||||
fromTime |
hour |
0 |
||
hundredth |
0 |
|||
minute |
0 |
|||
second |
0 |
|||
toTime |
hour |
23 |
||
hundredth |
99 |
|||
minute |
59 |
|||
second |
59 |
|||
|
The recipient registration mode defines how the OnSphere BACnet client is registered to receive event notifications from BACnet devices. NONE In this mode, OnSphere is not automatically registered as a notification recipient. The BACnet devices must be manually configured to include OnSphere in their recipientList. RECIPIENT_LIST_REGISTER In this mode, OnSphere automatically ensures that it is registered as a recipient on the BACnet devices. The getRecipient mechanism retrieves the current recipientList from the device, verifies whether OnSphere is already present, and adds it if necessary. This registration check is performed periodically, at a configurable interval, to detect and correct any missing or removed recipient entries. This guarantees that OnSphere remains registered and continues to receive event notifications reliably. Default value is [“RECIPIENT_LIST_REGISTER”] |
|||
type |
string |
|||
enum |
NONE, RECIPIENT_LIST_REGISTER |
|||
default |
RECIPIENT_LIST_REGISTER |
|||
|
At this interval, the BACnet client checks whether it is registered as a recipient on the device. This process generates communication with the target device for each configured notification by issuing GetRecipientList requests. The configured interval represents a tradeoff between network load and the speed at which the system can automatically re-register after a remote device reboot. A value of 0 (<1ms) disables this polling mechanism entirely. To minimize network traffic, an alternative approach is to use the NONE subscription method and manually configure the recipient registration directly on each device. Default value is [{“unit”:”SECONDS”,”value”:300}] |
|||
default |
unit |
SECONDS |
||
value |
300 |
|||
|
The module support the discovery of NotificationClass on the device, and automatically create subscription for them depending of the rule configuration. This functionality allowing to use the device as the source of configuration for alarming purpose. For more information about notification subscription rules ↗️. |
|||
type |
array |
|||
items |
||||
additionalProperties |
False |
|||
LinkedActionConfigurationEntity
type |
object |
||
properties |
|||
|
The itemId of the action.ospp to execute |
||
type |
string |
||
|
The duration after which the action will be timed out |
||
|
The module that will execute the action, this can be used for example if the action is a ping who can be executed by multiples instance of osp-network-monitor |
||
type |
string |
||
|
The parameters are allowing to choice the parameters who will be sent to the action. Each action required different parameters base on the type. |
||
type |
object |
||
additionalProperties |
oneOf |
||
additionalProperties |
False |
||
DurationConfigurationEntity
type |
object |
|
properties |
||
|
The unit of time expressed |
|
type |
string |
|
enum |
NANOSECONDS, MICROSECONDS, MILLISECONDS, SECONDS, MINUTES, HOURS, DAYS |
|
|
The amount of time expressed with the unit |
|
type |
integer |
|
additionalProperties |
False |
|
CONSTANT
type |
object |
|
properties |
||
|
type |
string |
enum |
CONSTANT |
|
default |
CONSTANT |
|
|
A constant value |
|
additionalProperties |
False |
|
LIST
type |
object |
||
properties |
|||
|
type |
string |
|
enum |
LIST |
||
default |
LIST |
||
|
A list of value accessors |
||
type |
array |
||
items |
oneOf |
||
additionalProperties |
False |
||
PROPERTIES
type |
object |
||
properties |
|||
|
type |
string |
|
enum |
PROPERTIES |
||
default |
PROPERTIES |
||
|
An object of value accessors |
||
type |
object |
||
additionalProperties |
oneOf |
||
additionalProperties |
False |
||
FIELD
type |
object |
|
properties |
||
|
type |
string |
enum |
FIELD |
|
default |
FIELD |
|
|
A field of the value |
|
type |
string |
|
enum |
ID, CONTENT, ERROR, TYPE, TIMESTAMP, NAME, DESCRIPTION |
|
|
An expression to access a field of the JSON content of the value |
|
type |
string |
|
additionalProperties |
False |
|
PropertiesEntity
type |
object |
|
properties |
||
|
type |
string |
additionalProperties |
False |
|
SubscriptionParameter
type |
object |
||
properties |
|||
|
In BACnet systems, object can transition between different states, such as “offnormal”, “fault”, and “normal”. This parameter allows you to specify which bacnetTransitions should trigger a LinkedAction. Warning This parameter is on the client side, meaning that the BACnet device must support and be configured for Intrinsic Reporting for the notifications to work as expected. Default value is [[“TO_OFF_NORMAL”,”TO_FAULT”,”TO_NORMAL”]] |
||
type |
array |
||
default |
TO_OFF_NORMAL |
||
TO_FAULT |
|||
TO_NORMAL |
|||
items |
type |
string |
|
enum |
TO_OFF_NORMAL, TO_FAULT, TO_NORMAL |
||
|
Define if the notification must use confirmation for the message transmission. Default value is [true] |
||
type |
boolean |
||
default |
True |
||
|
Define which days of the week the notification should be triggered. Default value is [[“MONDAY”,”TUESDAY”,”WEDNESDAY”,”THURSDAY”,”FRIDAY”,”SATURDAY”,”SUNDAY”]] |
||
type |
array |
||
default |
MONDAY |
||
TUESDAY |
|||
WEDNESDAY |
|||
THURSDAY |
|||
FRIDAY |
|||
SATURDAY |
|||
SUNDAY |
|||
items |
type |
string |
|
enum |
MONDAY, TUESDAY, WEDNESDAY, THURSDAY, FRIDAY, SATURDAY, SUNDAY |
||
|
Define the moment of the day when the notification should start being triggered. Default value is [{“hour”:0,”hundredth”:0,”minute”:0,”second”:0}] |
||
default |
hour |
0 |
|
hundredth |
0 |
||
minute |
0 |
||
second |
0 |
||
|
Define the moment of the day when the notification should stop being triggered. Default value is [{“hour”:23,”hundredth”:99,”minute”:59,”second”:59}] |
||
default |
hour |
23 |
|
hundredth |
99 |
||
minute |
59 |
||
second |
59 |
||
additionalProperties |
False |
||
Time
type |
object |
|
properties |
||
|
An hour of the day. |
|
type |
integer |
|
maximum |
23 |
|
minimum |
0 |
|
|
An hundredth of the second. |
|
type |
integer |
|
maximum |
99 |
|
minimum |
0 |
|
|
An minute of the hour. |
|
type |
integer |
|
maximum |
59 |
|
minimum |
0 |
|
|
An second of the minute. |
|
type |
integer |
|
maximum |
59 |
|
minimum |
0 |
|
additionalProperties |
False |
|
NotificationSubscriptionRules
type |
object |
||||
properties |
|||||
|
A textual description, only for documentation purpose |
||||
type |
string |
||||
|
Represents a selection of Bacnet object instances. You can select a single instance, e.g., “8” multiple instances, e.g., “8,9,12” or a range of instances, e.g., “2..4”. All these methods can be combined, e.g., “1,3..8,12,14..”. |
||||
type |
string |
||||
|
The action to execute when an notification is received. |
||||
|
Represents a selection of BACnet properties.
|
||||
oneOf |
type |
object |
|||
properties |
|||||
|
Represents a selection of BACnet property identifiers.
|
||||
type |
string |
||||
additionalProperties |
False |
||||
type |
object |
||||
properties |
|||||
|
Represents an explicit list of BACnet property names. This list contains standard BACnet property identifiers and allows precise selection of individual properties. |
||||
type |
array |
||||
items |
type |
string |
|||
enum |
ACKED_TRANSITIONS, ACK_REQUIRED, ACTION, ACTION_TEXT, ACTIVE_TEXT, ACTIVE_VT_SESSIONS, ALARM_VALUE, ALARM_VALUES, ALL, ALL_WRITES_SUCCESSFUL, APDU_SEGMENT_TIMEOUT, APDU_TIMEOUT, APPLICATION_SOFTWARE_VERSION, ARCHIVE, BIAS, CHANGE_OF_STATE_COUNT, CHANGE_OF_STATE_TIME, NOTIFICATION_CLASS, CONTROLLED_VARIABLE_REFERENCE, CONTROLLED_VARIABLE_UNITS, CONTROLLED_VARIABLE_VALUE, COV_INCREMENT, DATE_LIST, DAYLIGHT_SAVINGS_STATUS, DEADBAND, DERIVATIVE_CONSTANT, DERIVATIVE_CONSTANT_UNITS, DESCRIPTION, DESCRIPTION_OF_HALT, DEVICE_ADDRESS_BINDING, DEVICE_TYPE, EFFECTIVE_PERIOD, ELAPSED_ACTIVE_TIME, ERROR_LIMIT, EVENT_ENABLE, EVENT_STATE, EVENT_TYPE, EXCEPTION_SCHEDULE, FAULT_VALUES, FEEDBACK_VALUE, FILE_ACCESS_METHOD, FILE_SIZE, FILE_TYPE, FIRMWARE_REVISION, HIGH_LIMIT, INACTIVE_TEXT, IN_PROCESS, INSTANCE_OF, INTEGRAL_CONSTANT, INTEGRAL_CONSTANT_UNITS, LIMIT_ENABLE, LIST_OF_GROUP_MEMBERS, LIST_OF_OBJECT_PROPERTY_REFERENCES, LOCAL_DATE, LOCAL_TIME, LOCATION, LOW_LIMIT, MANIPULATED_VARIABLE_REFERENCE, MAXIMUM_OUTPUT, MAX_APDU_LENGTH_ACCEPTED, MAX_INFO_FRAMES, MAX_MASTER, MAX_PRES_VALUE, MINIMUM_OFF_TIME, MINIMUM_ON_TIME, MINIMUM_OUTPUT, MIN_PRES_VALUE, MODEL_NAME, MODIFICATION_DATE, NOTIFY_TYPE, NUMBER_OF_APDU_RETRIES, NUMBER_OF_STATES, OBJECT_IDENTIFIER, OBJECT_LIST, OBJECT_NAME, OBJECT_PROPERTY_REFERENCE, OBJECT_TYPE, OPTIONAL, OUT_OF_SERVICE, OUTPUT_UNITS, EVENT_PARAMETERS, POLARITY, PRESENT_VALUE, PRIORITY, PRIORITY_ARRAY, PRIORITY_FOR_WRITING, PROCESS_IDENTIFIER, PROGRAM_CHANGE, PROGRAM_LOCATION, PROGRAM_STATE, PROPORTIONAL_CONSTANT, PROPORTIONAL_CONSTANT_UNITS, PROTOCOL_OBJECT_TYPES_SUPPORTED, PROTOCOL_SERVICES_SUPPORTED, PROTOCOL_VERSION, READ_ONLY, REASON_FOR_HALT, RECIPIENT_LIST, RELIABILITY, RELINQUISH_DEFAULT, REQUIRED, RESOLUTION, SEGMENTATION_SUPPORTED, SETPOINT, SETPOINT_REFERENCE, STATE_TEXT, STATUS_FLAGS, SYSTEM_STATUS, TIME_DELAY, TIME_OF_ACTIVE_TIME_RESET, TIME_OF_STATE_COUNT_RESET, TIME_SYNCHRONIZATION_RECIPIENTS, UNITS, UPDATE_INTERVAL, UTC_OFFSET, VENDOR_IDENTIFIER, VENDOR_NAME, VT_CLASSES_SUPPORTED, WEEKLY_SCHEDULE, ATTEMPTED_SAMPLES, AVERAGE_VALUE, BUFFER_SIZE, CLIENT_COV_INCREMENT, COV_RESUBSCRIPTION_INTERVAL, EVENT_TIME_STAMPS, LOG_BUFFER, LOG_DEVICE_OBJECT_PROPERTY, ENABLE, LOG_INTERVAL, MAXIMUM_VALUE, MINIMUM_VALUE, NOTIFICATION_THRESHOLD, PROTOCOL_REVISION, RECORDS_SINCE_NOTIFICATION, RECORD_COUNT, START_TIME, STOP_TIME, STOP_WHEN_FULL, TOTAL_RECORD_COUNT, VALID_SAMPLES, WINDOW_INTERVAL, WINDOW_SAMPLES, MAXIMUM_VALUE_TIMESTAMP, MINIMUM_VALUE_TIMESTAMP, VARIANCE_VALUE, ACTIVE_COV_SUBSCRIPTIONS, BACKUP_FAILURE_TIMEOUT, CONFIGURATION_FILES, DATABASE_REVISION, DIRECT_READING, LAST_RESTORE_TIME, MAINTENANCE_REQUIRED, MEMBER_OF, MODE, OPERATION_EXPECTED, SETTING, SILENCED, TRACKING_VALUE, ZONE_MEMBERS, LIFE_SAFETY_ALARM_VALUES, MAX_SEGMENTS_ACCEPTED, PROFILE_NAME, AUTO_SLAVE_DISCOVERY, MANUAL_SLAVE_ADDRESS_BINDING, SLAVE_ADDRESS_BINDING, SLAVE_PROXY_ENABLE, LAST_NOTIFY_RECORD, SCHEDULE_DEFAULT, ACCEPTED_MODES, ADJUST_VALUE, COUNT, COUNT_BEFORE_CHANGE, COUNT_CHANGE_TIME, COV_PERIOD, INPUT_REFERENCE, LIMIT_MONITORING_INTERVAL, LOGGING_OBJECT, LOGGING_RECORD, PRESCALE, PULSE_RATE, SCALE, SCALE_FACTOR, UPDATE_TIME, VALUE_BEFORE_CHANGE, VALUE_SET, VALUE_CHANGE_TIME, ALIGN_INTERVALS, INTERVAL_OFFSET, LAST_RESTART_REASON, LOGGING_TYPE, RESTART_NOTIFICATION_RECIPIENTS, TIME_OF_DEVICE_RESTART, TIME_SYNCHRONIZATION_INTERVAL, TRIGGER, UTC_TIME_SYNCHRONIZATION_RECIPIENTS, NODE_SUBTYPE, NODE_TYPE, STRUCTURED_OBJECT_LIST, SUBORDINATE_ANNOTATIONS, SUBORDINATE_LIST, ACTUAL_SHED_LEVEL, DUTY_WINDOW, EXPECTED_SHED_LEVEL, FULL_DUTY_BASELINE, REQUESTED_SHED_LEVEL, SHED_DURATION, SHED_LEVEL_DESCRIPTIONS, SHED_LEVELS, STATE_DESCRIPTION, DOOR_ALARM_STATE, DOOR_EXTENDED_PULSE_TIME, DOOR_MEMBERS, DOOR_OPEN_TOO_LONG_TIME, DOOR_PULSE_TIME, DOOR_STATUS, DOOR_UNLOCK_DELAY_TIME, LOCK_STATUS, MASKED_ALARM_VALUES, SECURED_STATUS, ABSENTEE_LIMIT, ACCESS_ALARM_EVENTS, ACCESS_DOORS, ACCESS_EVENT, ACCESS_EVENT_AUTHENTICATION_FACTOR, ACCESS_EVENT_CREDENTIAL, ACCESS_EVENT_TIME, ACCESS_TRANSACTION_EVENTS, ACCOMPANIMENT, ACCOMPANIMENT_TIME, ACTIVATION_TIME, ACTIVE_AUTHENTICATION_POLICY, ASSIGNED_ACCESS_RIGHTS, AUTHENTICATION_FACTORS, AUTHENTICATION_POLICY_LIST, AUTHENTICATION_POLICY_NAMES, AUTHENTICATION_STATUS, AUTHORIZATION_MODE, BELONGS_TO, CREDENTIAL_DISABLE, CREDENTIAL_STATUS, CREDENTIALS, CREDENTIALS_IN_ZONE, DAYS_REMAINING, ENTRY_POINTS, EXIT_POINTS, EXPIRATION_TIME, EXTENDED_TIME_ENABLE, FAILED_ATTEMPT_EVENTS, FAILED_ATTEMPTS, FAILED_ATTEMPTS_TIME, LAST_ACCESS_EVENT, LAST_ACCESS_POINT, LAST_CREDENTIAL_ADDED, LAST_CREDENTIAL_ADDED_TIME, LAST_CREDENTIAL_REMOVED, LAST_CREDENTIAL_REMOVED_TIME, LAST_USE_TIME, LOCKOUT, LOCKOUT_RELINQUISH_TIME, MAX_FAILED_ATTEMPTS, MEMBERS, MUSTER_POINT, NEGATIVE_ACCESS_RULES, NUMBER_OF_AUTHENTICATION_POLICIES, OCCUPANCY_COUNT, OCCUPANCY_COUNT_ADJUST, OCCUPANCY_COUNT_ENABLE, OCCUPANCY_LOWER_LIMIT, OCCUPANCY_LOWER_LIMIT_ENFORCED, OCCUPANCY_STATE, OCCUPANCY_UPPER_LIMIT, OCCUPANCY_UPPER_LIMIT_ENFORCED, PASSBACK_MODE, PASSBACK_TIMEOUT, POSITIVE_ACCESS_RULES, REASON_FOR_DISABLE, SUPPORTED_FORMATS, SUPPORTED_FORMAT_CLASSES, THREAT_AUTHORITY, THREAT_LEVEL, TRACE_FLAG, TRANSACTION_NOTIFICATION_CLASS, USER_EXTERNAL_IDENTIFIER, USER_INFORMATION_REFERENCE, USER_NAME, USER_TYPE, USES_REMAINING, ZONE_FROM, ZONE_TO, ACCESS_EVENT_TAG, GLOBAL_IDENTIFIER, VERIFICATION_TIME, BASE_DEVICE_SECURITY_POLICY, DISTRIBUTION_KEY_REVISION, DO_NOT_HIDE, KEY_SETS, LAST_KEY_SERVER, NETWORK_ACCESS_SECURITY_POLICIES, PACKET_REORDER_TIME, SECURITY_PDU_TIMEOUT, SECURITY_TIME_WINDOW, SUPPORTED_SECURITY_ALGORITHMS, UPDATE_KEY_SET_TIMEOUT, BACKUP_AND_RESTORE_STATE, BACKUP_PREPARATION_TIME, RESTORE_COMPLETION_TIME, RESTORE_PREPARATION_TIME, BIT_MASK, BIT_TEXT, IS_UTC, GROUP_MEMBERS, GROUP_MEMBER_NAMES, MEMBER_STATUS_FLAGS, REQUESTED_UPDATE_INTERVAL, COVU_PERIOD, COVU_RECIPIENTS, EVENT_MESSAGE_TEXTS, EVENT_MESSAGE_TEXTS_CONFIG, EVENT_DETECTION_ENABLE, EVENT_ALGORITHM_INHIBIT, EVENT_ALGORITHM_INHIBIT_REF, TIME_DELAY_NORMAL, RELIABILITY_EVALUATION_INHIBIT, FAULT_PARAMETERS, FAULT_TYPE, LOCAL_FORWARDING_ONLY, PROCESS_IDENTIFIER_FILTER, SUBSCRIBED_RECIPIENTS, PORT_FILTER, AUTHORIZATION_EXEMPTIONS, ALLOW_GROUP_DELAY_INHIBIT, CHANNEL_NUMBER, CONTROL_GROUPS, EXECUTION_DELAY, LAST_PRIORITY, WRITE_STATUS, PROPERTY_LIST, SERIAL_NUMBER, BLINK_WARN_ENABLE, DEFAULT_FADE_TIME, DEFAULT_RAMP_RATE, DEFAULT_STEP_INCREMENT, EGRESS_TIME, IN_PROGRESS, INSTANTANEOUS_POWER, LIGHTING_COMMAND, LIGHTING_COMMAND_DEFAULT_PRIORITY, MAX_ACTUAL_VALUE, MIN_ACTUAL_VALUE, POWER, TRANSITION, EGRESS_ACTIVE, INTERFACE_VALUE, FAULT_HIGH_LIMIT, FAULT_LOW_LIMIT, LOW_DIFF_LIMIT, STRIKE_COUNT, TIME_OF_STRIKE_COUNT_RESET, DEFAULT_TIMEOUT, INITIAL_TIMEOUT, LAST_STATE_CHANGE, STATE_CHANGE_VALUES, TIMER_RUNNING, TIMER_STATE, APDU_LENGTH, IP_ADDRESS, IP_DEFAULT_GATEWAY, IP_DHCP_ENABLE, IP_DHCP_LEASE_TIME, IP_DHCP_LEASE_TIME_REMAINING, IP_DHCP_SERVER, IP_DNS_SERVER, BACNET_IP_GLOBAL_ADDRESS, BACNET_IP_MODE, BACNET_IP_MULTICAST_ADDRESS, BACNET_IP_NAT_TRAVERSAL, IP_SUBNET_MASK, BACNET_IP_UDP_PORT, BBMD_ACCEPT_FD_REGISTRATIONS, BBMD_BROADCAST_DISTRIBUTION_TABLE, BBMD_FOREIGN_DEVICE_TABLE, CHANGES_PENDING, COMMAND, FD_BBMD_ADDRESS, FD_SUBSCRIPTION_LIFETIME, LINK_SPEED, LINK_SPEEDS, LINK_SPEED_AUTONEGOTIATE, MAC_ADDRESS, NETWORK_INTERFACE_NAME, NETWORK_NUMBER, NETWORK_NUMBER_QUALITY, NETWORK_TYPE, ROUTING_TABLE, VIRTUAL_MAC_ADDRESS_TABLE, COMMAND_TIME_ARRAY, CURRENT_COMMAND_PRIORITY, LAST_COMMAND_TIME, VALUE_SOURCE, VALUE_SOURCE_ARRAY, BACNET_IPV6_MODE, IPV6_ADDRESS, IPV6_PREFIX_LENGTH, BACNET_IPV6_UDP_PORT, IPV6_DEFAULT_GATEWAY, BACNET_IPV6_MULTICAST_ADDRESS, IPV6_DNS_SERVER, IPV6_AUTO_ADDRESSING_ENABLE, IPV6_DHCP_LEASE_TIME, IPV6_DHCP_LEASE_TIME_REMAINING, IPV6_DHCP_SERVER, IPV6_ZONE_INDEX, ASSIGNED_LANDING_CALLS, CAR_ASSIGNED_DIRECTION, CAR_DOOR_COMMAND, CAR_DOOR_STATUS, CAR_DOOR_TEXT, CAR_DOOR_ZONE, CAR_DRIVE_STATUS, CAR_LOAD, CAR_LOAD_UNITS, CAR_MODE, CAR_MOVING_DIRECTION, CAR_POSITION, ELEVATOR_GROUP, ENERGY_METER, ENERGY_METER_REF, ESCALATOR_MODE, FAULT_SIGNALS, FLOOR_TEXT, GROUP_ID, GROUP_MODE, HIGHER_DECK, INSTALLATION_ID, LANDING_CALLS, LANDING_CALL_CONTROL, LANDING_DOOR_STATUS, LOWER_DECK, MACHINE_ROOM_ID, MAKING_CAR_CALL, NEXT_STOPPING_FLOOR, OPERATION_DIRECTION, PASSENGER_ALARM, POWER_MODE, REGISTERED_CAR_CALL, ACTIVE_COV_MULTIPLE_SUBSCRIPTIONS, PROTOCOL_LEVEL, REFERENCE_PORT, DEPLOYED_PROFILE_LOCATION, PROFILE_LOCATION, TAGS, SUBORDINATE_NODE_TYPES, SUBORDINATE_TAGS, SUBORDINATE_RELATIONSHIPS, DEFAULT_SUBORDINATE_RELATIONSHIP, REPRESENTS |
||||
additionalProperties |
False |
||||
|
The BACnet process identifier associated with this notification recipient. This integer uniquely identifies the process or application instance within the BACnet network that should handle the notification. It allows the system to route the notification to the correct recipient process, ensuring that actions linked to this notification are executed by the intended process. |
||||
type |
integer |
||||
|
The parameter of the subscription like the transition to react on and when to react. |
||||
additionalProperties |
False |
||||
PropertiesAcquisitionRules
type |
object |
|
properties |
||
|
The module support the discovery of BACnet objects on the device, and automatically create property acquisition for them depending of the rule configuration. This functionality allowing to use the device as the source of configuration for data acquisition. |
|
type |
array |
|
items |
||
|
Default linked action executed when property acquisition rules are applied. If a specific linked action is defined in the acquisition rule, this default linked action will be overridden. |
|
|
Default read strategy applied to property acquisition rules. If a specific mode is defined in the acquisition rule, this default mode will be overridden. |
|
oneOf |
||
additionalProperties |
False |
|
PropertyAcquisitionRules
type |
object |
|
properties |
||
|
Optional human-readable description intended for documentation and configuration clarity. This field has no functional impact on execution. It is useful to explain the purpose of the acquisition rule, especially in complex configurations with multiple rules. |
|
type |
string |
|
|
List of rules defining which BACnet properties must be acquired. Each rule specifies the object types, instance IDs, and properties to be acquired. |
|
type |
array |
|
items |
||
|
Optional action to be executed when the acquisition rule is applied. If not specified, the default linked action is applied. |
|
|
Strategy defining how the BACnet properties are read from the device. If not specified, the default read strategy is applied. |
|
oneOf |
||
additionalProperties |
False |
|
PropertyIncludeRules
type |
object |
||||
properties |
|||||
|
Represents a selection of BACnet object instances. You can select a single instance, e.g., “8” multiple instances, e.g., “8,9,12” or a range of instances, e.g., “2..4”. All these methods can be combined, e.g., “1,3..8,12,14..”. |
||||
type |
string |
||||
|
Represents a selection of BACnet object types. The object types can be selected either by specifying a range of numeric object type identifiers or by providing an explicit list of object type names. Only one selection method can be used at a time. |
||||
oneOf |
type |
object |
|||
properties |
|||||
|
Represents a selection of BACnet object types. You can select a single object type using its numeric identifier, e.g., “2”, multiple object types, e.g., “2,5,8”, or a range of object types, e.g., “1..5”. For ranges, the start or end can be left open, e.g., “..3” or “7..”. All these methods can be combined, e.g., “0,2..6,10,15..”. |
||||
type |
string |
||||
additionalProperties |
False |
||||
type |
object |
||||
properties |
|||||
|
Represents a list of BACnet object types. This list can include standard BACnet object types, such as “ANALOG_VALUE”, or their numeric identifiers, which is useful for vendor-specific object types. |
||||
type |
array |
||||
items |
type |
string |
|||
enum |
ANALOG_INPUT, ANALOG_OUTPUT, ANALOG_VALUE, BINARY_INPUT, BINARY_OUTPUT, BINARY_VALUE, CALENDAR, COMMAND, DEVICE, EVENT_ENROLLMENT, FILE, GROUP, LOOP, MULTI_STATE_INPUT, MULTI_STATE_OUTPUT, NOTIFICATION_CLASS, PROGRAM, SCHEDULE, AVERAGING, MULTI_STATE_VALUE, TREND_LOG, LIFE_SAFETY_POINT, LIFE_SAFETY_ZONE, ACCUMULATOR, PULSE_CONVERTER, EVENT_LOG, GLOBAL_GROUP, TREND_LOG_MULTIPLE, LOAD_CONTROL, STRUCTURED_VIEW, ACCESS_DOOR, TIMER, ACCESS_CREDENTIAL, ACCESS_POINT, ACCESS_RIGHTS, ACCESS_USER, ACCESS_ZONE, CREDENTIAL_DATA_INPUT, NETWORK_SECURITY, BITSTRING_VALUE, CHARACTERSTRING_VALUE, DATE_PATTERN_VALUE, DATE_VALUE, DATETIME_PATTERN_VALUE, DATETIME_VALUE, INTEGER_VALUE, LARGE_ANALOG_VALUE, OCTETSTRING_VALUE, POSITIVE_INTEGER_VALUE, TIME_PATTERN_VALUE, TIME_VALUE, NOTIFICATION_FORWARDER, ALERT_ENROLLMENT, CHANNEL, LIGHTING_OUTPUT, BINARY_LIGHTING_OUTPUT, NETWORK_PORT, ELEVATOR_GROUP, ESCALATOR, LIFT |
||||
additionalProperties |
False |
||||
|
Represents a selection of BACnet properties.
|
||||
oneOf |
type |
object |
|||
properties |
|||||
|
Represents a selection of BACnet property identifiers.
|
||||
type |
string |
||||
additionalProperties |
False |
||||
type |
object |
||||
properties |
|||||
|
Represents an explicit list of BACnet property names. This list contains standard BACnet property identifiers and allows precise selection of individual properties. |
||||
type |
array |
||||
items |
type |
string |
|||
enum |
ACKED_TRANSITIONS, ACK_REQUIRED, ACTION, ACTION_TEXT, ACTIVE_TEXT, ACTIVE_VT_SESSIONS, ALARM_VALUE, ALARM_VALUES, ALL, ALL_WRITES_SUCCESSFUL, APDU_SEGMENT_TIMEOUT, APDU_TIMEOUT, APPLICATION_SOFTWARE_VERSION, ARCHIVE, BIAS, CHANGE_OF_STATE_COUNT, CHANGE_OF_STATE_TIME, NOTIFICATION_CLASS, CONTROLLED_VARIABLE_REFERENCE, CONTROLLED_VARIABLE_UNITS, CONTROLLED_VARIABLE_VALUE, COV_INCREMENT, DATE_LIST, DAYLIGHT_SAVINGS_STATUS, DEADBAND, DERIVATIVE_CONSTANT, DERIVATIVE_CONSTANT_UNITS, DESCRIPTION, DESCRIPTION_OF_HALT, DEVICE_ADDRESS_BINDING, DEVICE_TYPE, EFFECTIVE_PERIOD, ELAPSED_ACTIVE_TIME, ERROR_LIMIT, EVENT_ENABLE, EVENT_STATE, EVENT_TYPE, EXCEPTION_SCHEDULE, FAULT_VALUES, FEEDBACK_VALUE, FILE_ACCESS_METHOD, FILE_SIZE, FILE_TYPE, FIRMWARE_REVISION, HIGH_LIMIT, INACTIVE_TEXT, IN_PROCESS, INSTANCE_OF, INTEGRAL_CONSTANT, INTEGRAL_CONSTANT_UNITS, LIMIT_ENABLE, LIST_OF_GROUP_MEMBERS, LIST_OF_OBJECT_PROPERTY_REFERENCES, LOCAL_DATE, LOCAL_TIME, LOCATION, LOW_LIMIT, MANIPULATED_VARIABLE_REFERENCE, MAXIMUM_OUTPUT, MAX_APDU_LENGTH_ACCEPTED, MAX_INFO_FRAMES, MAX_MASTER, MAX_PRES_VALUE, MINIMUM_OFF_TIME, MINIMUM_ON_TIME, MINIMUM_OUTPUT, MIN_PRES_VALUE, MODEL_NAME, MODIFICATION_DATE, NOTIFY_TYPE, NUMBER_OF_APDU_RETRIES, NUMBER_OF_STATES, OBJECT_IDENTIFIER, OBJECT_LIST, OBJECT_NAME, OBJECT_PROPERTY_REFERENCE, OBJECT_TYPE, OPTIONAL, OUT_OF_SERVICE, OUTPUT_UNITS, EVENT_PARAMETERS, POLARITY, PRESENT_VALUE, PRIORITY, PRIORITY_ARRAY, PRIORITY_FOR_WRITING, PROCESS_IDENTIFIER, PROGRAM_CHANGE, PROGRAM_LOCATION, PROGRAM_STATE, PROPORTIONAL_CONSTANT, PROPORTIONAL_CONSTANT_UNITS, PROTOCOL_OBJECT_TYPES_SUPPORTED, PROTOCOL_SERVICES_SUPPORTED, PROTOCOL_VERSION, READ_ONLY, REASON_FOR_HALT, RECIPIENT_LIST, RELIABILITY, RELINQUISH_DEFAULT, REQUIRED, RESOLUTION, SEGMENTATION_SUPPORTED, SETPOINT, SETPOINT_REFERENCE, STATE_TEXT, STATUS_FLAGS, SYSTEM_STATUS, TIME_DELAY, TIME_OF_ACTIVE_TIME_RESET, TIME_OF_STATE_COUNT_RESET, TIME_SYNCHRONIZATION_RECIPIENTS, UNITS, UPDATE_INTERVAL, UTC_OFFSET, VENDOR_IDENTIFIER, VENDOR_NAME, VT_CLASSES_SUPPORTED, WEEKLY_SCHEDULE, ATTEMPTED_SAMPLES, AVERAGE_VALUE, BUFFER_SIZE, CLIENT_COV_INCREMENT, COV_RESUBSCRIPTION_INTERVAL, EVENT_TIME_STAMPS, LOG_BUFFER, LOG_DEVICE_OBJECT_PROPERTY, ENABLE, LOG_INTERVAL, MAXIMUM_VALUE, MINIMUM_VALUE, NOTIFICATION_THRESHOLD, PROTOCOL_REVISION, RECORDS_SINCE_NOTIFICATION, RECORD_COUNT, START_TIME, STOP_TIME, STOP_WHEN_FULL, TOTAL_RECORD_COUNT, VALID_SAMPLES, WINDOW_INTERVAL, WINDOW_SAMPLES, MAXIMUM_VALUE_TIMESTAMP, MINIMUM_VALUE_TIMESTAMP, VARIANCE_VALUE, ACTIVE_COV_SUBSCRIPTIONS, BACKUP_FAILURE_TIMEOUT, CONFIGURATION_FILES, DATABASE_REVISION, DIRECT_READING, LAST_RESTORE_TIME, MAINTENANCE_REQUIRED, MEMBER_OF, MODE, OPERATION_EXPECTED, SETTING, SILENCED, TRACKING_VALUE, ZONE_MEMBERS, LIFE_SAFETY_ALARM_VALUES, MAX_SEGMENTS_ACCEPTED, PROFILE_NAME, AUTO_SLAVE_DISCOVERY, MANUAL_SLAVE_ADDRESS_BINDING, SLAVE_ADDRESS_BINDING, SLAVE_PROXY_ENABLE, LAST_NOTIFY_RECORD, SCHEDULE_DEFAULT, ACCEPTED_MODES, ADJUST_VALUE, COUNT, COUNT_BEFORE_CHANGE, COUNT_CHANGE_TIME, COV_PERIOD, INPUT_REFERENCE, LIMIT_MONITORING_INTERVAL, LOGGING_OBJECT, LOGGING_RECORD, PRESCALE, PULSE_RATE, SCALE, SCALE_FACTOR, UPDATE_TIME, VALUE_BEFORE_CHANGE, VALUE_SET, VALUE_CHANGE_TIME, ALIGN_INTERVALS, INTERVAL_OFFSET, LAST_RESTART_REASON, LOGGING_TYPE, RESTART_NOTIFICATION_RECIPIENTS, TIME_OF_DEVICE_RESTART, TIME_SYNCHRONIZATION_INTERVAL, TRIGGER, UTC_TIME_SYNCHRONIZATION_RECIPIENTS, NODE_SUBTYPE, NODE_TYPE, STRUCTURED_OBJECT_LIST, SUBORDINATE_ANNOTATIONS, SUBORDINATE_LIST, ACTUAL_SHED_LEVEL, DUTY_WINDOW, EXPECTED_SHED_LEVEL, FULL_DUTY_BASELINE, REQUESTED_SHED_LEVEL, SHED_DURATION, SHED_LEVEL_DESCRIPTIONS, SHED_LEVELS, STATE_DESCRIPTION, DOOR_ALARM_STATE, DOOR_EXTENDED_PULSE_TIME, DOOR_MEMBERS, DOOR_OPEN_TOO_LONG_TIME, DOOR_PULSE_TIME, DOOR_STATUS, DOOR_UNLOCK_DELAY_TIME, LOCK_STATUS, MASKED_ALARM_VALUES, SECURED_STATUS, ABSENTEE_LIMIT, ACCESS_ALARM_EVENTS, ACCESS_DOORS, ACCESS_EVENT, ACCESS_EVENT_AUTHENTICATION_FACTOR, ACCESS_EVENT_CREDENTIAL, ACCESS_EVENT_TIME, ACCESS_TRANSACTION_EVENTS, ACCOMPANIMENT, ACCOMPANIMENT_TIME, ACTIVATION_TIME, ACTIVE_AUTHENTICATION_POLICY, ASSIGNED_ACCESS_RIGHTS, AUTHENTICATION_FACTORS, AUTHENTICATION_POLICY_LIST, AUTHENTICATION_POLICY_NAMES, AUTHENTICATION_STATUS, AUTHORIZATION_MODE, BELONGS_TO, CREDENTIAL_DISABLE, CREDENTIAL_STATUS, CREDENTIALS, CREDENTIALS_IN_ZONE, DAYS_REMAINING, ENTRY_POINTS, EXIT_POINTS, EXPIRATION_TIME, EXTENDED_TIME_ENABLE, FAILED_ATTEMPT_EVENTS, FAILED_ATTEMPTS, FAILED_ATTEMPTS_TIME, LAST_ACCESS_EVENT, LAST_ACCESS_POINT, LAST_CREDENTIAL_ADDED, LAST_CREDENTIAL_ADDED_TIME, LAST_CREDENTIAL_REMOVED, LAST_CREDENTIAL_REMOVED_TIME, LAST_USE_TIME, LOCKOUT, LOCKOUT_RELINQUISH_TIME, MAX_FAILED_ATTEMPTS, MEMBERS, MUSTER_POINT, NEGATIVE_ACCESS_RULES, NUMBER_OF_AUTHENTICATION_POLICIES, OCCUPANCY_COUNT, OCCUPANCY_COUNT_ADJUST, OCCUPANCY_COUNT_ENABLE, OCCUPANCY_LOWER_LIMIT, OCCUPANCY_LOWER_LIMIT_ENFORCED, OCCUPANCY_STATE, OCCUPANCY_UPPER_LIMIT, OCCUPANCY_UPPER_LIMIT_ENFORCED, PASSBACK_MODE, PASSBACK_TIMEOUT, POSITIVE_ACCESS_RULES, REASON_FOR_DISABLE, SUPPORTED_FORMATS, SUPPORTED_FORMAT_CLASSES, THREAT_AUTHORITY, THREAT_LEVEL, TRACE_FLAG, TRANSACTION_NOTIFICATION_CLASS, USER_EXTERNAL_IDENTIFIER, USER_INFORMATION_REFERENCE, USER_NAME, USER_TYPE, USES_REMAINING, ZONE_FROM, ZONE_TO, ACCESS_EVENT_TAG, GLOBAL_IDENTIFIER, VERIFICATION_TIME, BASE_DEVICE_SECURITY_POLICY, DISTRIBUTION_KEY_REVISION, DO_NOT_HIDE, KEY_SETS, LAST_KEY_SERVER, NETWORK_ACCESS_SECURITY_POLICIES, PACKET_REORDER_TIME, SECURITY_PDU_TIMEOUT, SECURITY_TIME_WINDOW, SUPPORTED_SECURITY_ALGORITHMS, UPDATE_KEY_SET_TIMEOUT, BACKUP_AND_RESTORE_STATE, BACKUP_PREPARATION_TIME, RESTORE_COMPLETION_TIME, RESTORE_PREPARATION_TIME, BIT_MASK, BIT_TEXT, IS_UTC, GROUP_MEMBERS, GROUP_MEMBER_NAMES, MEMBER_STATUS_FLAGS, REQUESTED_UPDATE_INTERVAL, COVU_PERIOD, COVU_RECIPIENTS, EVENT_MESSAGE_TEXTS, EVENT_MESSAGE_TEXTS_CONFIG, EVENT_DETECTION_ENABLE, EVENT_ALGORITHM_INHIBIT, EVENT_ALGORITHM_INHIBIT_REF, TIME_DELAY_NORMAL, RELIABILITY_EVALUATION_INHIBIT, FAULT_PARAMETERS, FAULT_TYPE, LOCAL_FORWARDING_ONLY, PROCESS_IDENTIFIER_FILTER, SUBSCRIBED_RECIPIENTS, PORT_FILTER, AUTHORIZATION_EXEMPTIONS, ALLOW_GROUP_DELAY_INHIBIT, CHANNEL_NUMBER, CONTROL_GROUPS, EXECUTION_DELAY, LAST_PRIORITY, WRITE_STATUS, PROPERTY_LIST, SERIAL_NUMBER, BLINK_WARN_ENABLE, DEFAULT_FADE_TIME, DEFAULT_RAMP_RATE, DEFAULT_STEP_INCREMENT, EGRESS_TIME, IN_PROGRESS, INSTANTANEOUS_POWER, LIGHTING_COMMAND, LIGHTING_COMMAND_DEFAULT_PRIORITY, MAX_ACTUAL_VALUE, MIN_ACTUAL_VALUE, POWER, TRANSITION, EGRESS_ACTIVE, INTERFACE_VALUE, FAULT_HIGH_LIMIT, FAULT_LOW_LIMIT, LOW_DIFF_LIMIT, STRIKE_COUNT, TIME_OF_STRIKE_COUNT_RESET, DEFAULT_TIMEOUT, INITIAL_TIMEOUT, LAST_STATE_CHANGE, STATE_CHANGE_VALUES, TIMER_RUNNING, TIMER_STATE, APDU_LENGTH, IP_ADDRESS, IP_DEFAULT_GATEWAY, IP_DHCP_ENABLE, IP_DHCP_LEASE_TIME, IP_DHCP_LEASE_TIME_REMAINING, IP_DHCP_SERVER, IP_DNS_SERVER, BACNET_IP_GLOBAL_ADDRESS, BACNET_IP_MODE, BACNET_IP_MULTICAST_ADDRESS, BACNET_IP_NAT_TRAVERSAL, IP_SUBNET_MASK, BACNET_IP_UDP_PORT, BBMD_ACCEPT_FD_REGISTRATIONS, BBMD_BROADCAST_DISTRIBUTION_TABLE, BBMD_FOREIGN_DEVICE_TABLE, CHANGES_PENDING, COMMAND, FD_BBMD_ADDRESS, FD_SUBSCRIPTION_LIFETIME, LINK_SPEED, LINK_SPEEDS, LINK_SPEED_AUTONEGOTIATE, MAC_ADDRESS, NETWORK_INTERFACE_NAME, NETWORK_NUMBER, NETWORK_NUMBER_QUALITY, NETWORK_TYPE, ROUTING_TABLE, VIRTUAL_MAC_ADDRESS_TABLE, COMMAND_TIME_ARRAY, CURRENT_COMMAND_PRIORITY, LAST_COMMAND_TIME, VALUE_SOURCE, VALUE_SOURCE_ARRAY, BACNET_IPV6_MODE, IPV6_ADDRESS, IPV6_PREFIX_LENGTH, BACNET_IPV6_UDP_PORT, IPV6_DEFAULT_GATEWAY, BACNET_IPV6_MULTICAST_ADDRESS, IPV6_DNS_SERVER, IPV6_AUTO_ADDRESSING_ENABLE, IPV6_DHCP_LEASE_TIME, IPV6_DHCP_LEASE_TIME_REMAINING, IPV6_DHCP_SERVER, IPV6_ZONE_INDEX, ASSIGNED_LANDING_CALLS, CAR_ASSIGNED_DIRECTION, CAR_DOOR_COMMAND, CAR_DOOR_STATUS, CAR_DOOR_TEXT, CAR_DOOR_ZONE, CAR_DRIVE_STATUS, CAR_LOAD, CAR_LOAD_UNITS, CAR_MODE, CAR_MOVING_DIRECTION, CAR_POSITION, ELEVATOR_GROUP, ENERGY_METER, ENERGY_METER_REF, ESCALATOR_MODE, FAULT_SIGNALS, FLOOR_TEXT, GROUP_ID, GROUP_MODE, HIGHER_DECK, INSTALLATION_ID, LANDING_CALLS, LANDING_CALL_CONTROL, LANDING_DOOR_STATUS, LOWER_DECK, MACHINE_ROOM_ID, MAKING_CAR_CALL, NEXT_STOPPING_FLOOR, OPERATION_DIRECTION, PASSENGER_ALARM, POWER_MODE, REGISTERED_CAR_CALL, ACTIVE_COV_MULTIPLE_SUBSCRIPTIONS, PROTOCOL_LEVEL, REFERENCE_PORT, DEPLOYED_PROFILE_LOCATION, PROFILE_LOCATION, TAGS, SUBORDINATE_NODE_TYPES, SUBORDINATE_TAGS, SUBORDINATE_RELATIONSHIPS, DEFAULT_SUBORDINATE_RELATIONSHIP, REPRESENTS |
||||
additionalProperties |
False |
||||
additionalProperties |
False |
||||
ObjectTypesEntity
type |
object |
|
properties |
||
|
type |
string |
additionalProperties |
False |
|
PROPERTY_SUBSCRIPTION
type |
object |
|
properties |
||
|
type |
string |
enum |
PROPERTY_SUBSCRIPTION |
|
default |
PROPERTY_SUBSCRIPTION |
|
|
When a BACnet COV Subscribe request is sent, a COV increment value may be included. This value defines the minimum change required for the controller to generate a COV notification. If the COV increment is specified in the subscription configuration file, it will override the COV increment value locally configured in the controller for the duration of the subscription. As a result, the controller will use the COV increment provided by the subscriber to determine when COV notifications are triggered. Care must therefore be taken when configuring this parameter, as an inappropriate value may alter the expected behavior of COV reporting and impact system performance or data accuracy. |
|
type |
number |
|
|
In a BACnet system, COV (Change of Value) subscription frequency defines how often a subscribing device renews its subscription to receive value change notifications from a BACnet controller. This parameter does not control how often COV notifications are sent, but how frequently the subscription request is reissued to keep the subscription active. Subscription validity, expressed as a lifetime or timeout, defines the maximum duration for which a COV subscription remains active without renewal. If the subscription is not refreshed before the validity period expires, the controller automatically cancels the subscription and stops sending COV notifications. The COV subscription frequency represents a tradeoff between network load and fault detection time. A higher subscription frequency increases network traffic but reduces the time required to detect a controller failure or communication loss. Conversely, a lower subscription frequency minimizes network load but increases the duration during which a controller may remain unreachable before the subscription expires. The subscription frequency must therefore be carefully balanced to ensure both network efficiency and acceptable fault detection latency. |
|
|
In a BACnet COV mechanism, the validity value (subscription lifetime) is transmitted to the controller with each COV Subscribe request. This value defines the maximum time the controller shall maintain the subscription without receiving a renewal request. To ensure uninterrupted COV notifications, the validity value must be configured greater than the subscription renewal frequency. As a best practice, the validity period should be at least three times longer than the subscription frequency. This margin accounts for communication delays, network congestion, or temporary device unavailability, and prevents unintended subscription expiration. If the validity period is too short compared to the subscription frequency, missed or delayed Subscribe requests may cause the controller to cancel the subscription, resulting in loss of COV updates. If no value is provided, the default is set to three times the subscription frequency. |
|
additionalProperties |
False |
|
OBJECT_SUBSCRIPTION
type |
object |
|
properties |
||
|
type |
string |
enum |
OBJECT_SUBSCRIPTION |
|
default |
OBJECT_SUBSCRIPTION |
|
|
In a BACnet system, COV (Change of Value) subscription frequency defines how often a subscribing device renews its subscription to receive value change notifications from a BACnet controller. This parameter does not control how often COV notifications are sent, but how frequently the subscription request is reissued to keep the subscription active. Subscription validity, expressed as a lifetime or timeout, defines the maximum duration for which a COV subscription remains active without renewal. If the subscription is not refreshed before the validity period expires, the controller automatically cancels the subscription and stops sending COV notifications. The COV subscription frequency represents a tradeoff between network load and fault detection time. A higher subscription frequency increases network traffic but reduces the time required to detect a controller failure or communication loss. Conversely, a lower subscription frequency minimizes network load but increases the duration during which a controller may remain unreachable before the subscription expires. The subscription frequency must therefore be carefully balanced to ensure both network efficiency and acceptable fault detection latency. |
|
|
In a BACnet COV mechanism, the validity value (subscription lifetime) is transmitted to the controller with each COV Subscribe request. This value defines the maximum time the controller shall maintain the subscription without receiving a renewal request. If the validity period is too short compared to the subscription frequency, missed or delayed Subscribe requests may cause the controller to cancel the subscription, resulting in loss of COV updates. To ensure uninterrupted COV notifications, the validity value must be configured greater than the subscription renewal frequency. As a best practice, the validity period should be at least three times longer than the subscription frequency. This margin accounts for communication delays, network congestion, or temporary device unavailability, and prevents unintended subscription expiration. If no value is provided, the default is set to three times the subscription frequency. |
|
additionalProperties |
False |
|
MULTIPLE_POLLING
type |
object |
|
properties |
||
|
type |
string |
enum |
MULTIPLE_POLLING |
|
default |
MULTIPLE_POLLING |
|
|
Polling frequency defines how often a BACnet supervisory system reads data from a controller. A higher polling rate provides faster updates and quicker detection of changes but increases network traffic and may impact communication performance. A lower polling rate reduces network load but results in slower data updates. The polling frequency should be configured according to data criticality, network type, and system size to ensure reliable and efficient BACnet communication. |
|
additionalProperties |
False |
|
SINGLE_POLLING
type |
object |
|
properties |
||
|
type |
string |
enum |
SINGLE_POLLING |
|
default |
SINGLE_POLLING |
|
|
Polling frequency defines how often a BACnet supervisory system reads data from a controller. A higher polling rate provides faster updates and quicker detection of changes but increases network traffic and may impact communication performance. A lower polling rate reduces network load but results in slower data updates. The polling frequency should be configured according to data criticality, network type, and system size to ensure reliable and efficient BACnet communication. |
|
additionalProperties |
False |
|
DeviceSupervisionEntity
type |
object |
||
properties |
|||
|
Delay in milliseconds between each retry attempt during connectivity checks. The default value is 500 milliseconds. Default value is [{“unit”:”MILLISECONDS”,”value”:500}] |
||
default |
unit |
MILLISECONDS |
|
value |
500 |
||
|
Maximum number of retries for each connectivity check before reporting an error. The default value is 3 retries. Default value is [3] |
||
type |
integer |
||
default |
3 |
||
|
This supervision method is used to monitor the connection status and to detect any configuration changes that may have occurred since the previous check.
Default value is [“OBJECT_NAME”] |
||
type |
string |
||
enum |
FORCE_CONNECTED, OBJECT_NAME, TIME_OF_DEVICE_RESTART |
||
default |
OBJECT_NAME |
||
|
Interval between check of the device connection or connection change detection Default value is 30 seconds. Default value is [{“unit”:”SECONDS”,”value”:30}] |
||
default |
unit |
SECONDS |
|
value |
30 |
||
|
This value helps prevent excessive load on the BACnet network during module restarts when many devices are involved by enabling batch processing based on device criticality. The initial connexion will be random between 0 and the value set. The default value is 0 seconds. Default value is [{“unit”:”SECONDS”,”value”:0}] |
||
default |
unit |
SECONDS |
|
value |
0 |
||
additionalProperties |